Product

PRODUCTS
SZ18 On-Load Tap-Changing Energy-Saving Power Transformer
SZ18 On-Load Tap-Changing Energy-Saving Power Transformer
+
  • SZ18 On-Load Tap-Changing Energy-Saving Power Transformer
  • SZ18 On-Load Tap-Changing Energy-Saving Power Transformer

SZ18 On-Load Tap-Changing Energy-Saving Power Transformer


Our company produces the SZ18 (20, 22) series 35kV class on-load tap-changing energy-saving power transformers, whose performance complies with GB20052-2020 "Energy Efficiency Limits and Energy Efficiency Grades for Power Transformers" and GB/T6451 "Technical Parameters and Requirements for Three-phase Oil-immersed Power Transformers" standards.

Keywords:

Product Details Product parameters

1. Product Introduction:

Our company produces the SZ18(20, 22) series 35kV class on-load tap-changing energy-saving power transformers. Their performance complies with GB20052-2020 "Energy Efficiency Limits and Energy Efficiency Grades for Power Transformers" and GB/T6451 "Technical Parameters and Requirements for Three-phase Oil-immersed Power Transformers" standards. The core uses high-quality cold-rolled silicon steel sheets, and the windings are made of high-quality oxygen-free copper. The appearance is beautiful, operation is safe, and they are widely used in urban and rural industrial and agricultural power grids.

2. Standards:

2.1 IEC60076-1 Power Transformers

2.2 GB/T1094.1 Power Transformers

2.3 GB/T6451 Technical Parameters and Requirements for Oil-immersed Power Transformers

2.4 JB/T10088 Sound Level of 6kV~500kV Power Transformers

2.5 GB20052-2020 Energy Efficiency Limits and Energy Efficiency Grades for Power Transformers

3. Model and Meaning:

4. Performance and Structural Features:

4.1 High reliability, advanced performance level, and reasonable economic indicators.

4.2 The core adopts a stepped three-level or five-level joint, with surface coated with cured paint to reduce loss and noise.

4.3 The winding structure is novel, the oil channel design is reasonable, and a new insulation structure is used to improve mechanical strength and short-circuit resistance.

4.4 The oil tank adopts a corrugated form, with diverse, beautiful, and elegant structures.

4.5 Equipped with remote monitoring function to grasp the equipment operating status in real time.

Technical Parameters of S13 Series 35kV Class On-load Tap Changer Energy-Saving Distribution Transformer

Transformer Capacity (kVA)High Voltage 
(kV)
High Voltage Tap Range 
(%)
Low Voltage 
(kV)
Rated 
Frequency 
(Hz)
Connection Group NumberNo Load 
Loss (W)
Load 
Loss (W)
No Load Current 
(%)
Short Circuit 
Impedance 
(%)
50

 

 

 

 

35
38.5

 

 

 

 

2×2.5 
5

 

 

 

 

0.4

 

 

 

 

50

 

 

 

 

Dyn11 Yyn0

1301200/11401.25

 

 

 

 

6.5

1001852010/19101.05
1252152370/22601.05
1602252820/26800.95
2002703320/31600.95
2503203950/37600.9
3153854750/45300.9
4004655740/54700.8
5005456910/65800.8
63066578600.62
80078594000.62
1000920115000.62
1250112013900.57
16001350166000.57
20001590197000.52
25001890232000.52

Technical Parameters of SZ18(20, 22) Series 35kV Class On-Load Tap Changer Energy-Saving Power Transformer

Rated Capacity 
kVA
Voltage Combination and Tap RangeRated 
Frequency 
(Hz)
Connection Group NumberNo Load 
Loss (W)
Load 
Loss (W)
No Load 
Loss (W)
Load 
Loss (W)
No Load 
Loss (W)
Load 
Loss (W)

Short Circuit Impedance (%)

High Voltage 
(kV)
High Voltage Tap Range 
(%)
Low Voltage 
(kV)
SZ 18SZ 20SZ 22
3150

 

35~38.5

 

3×2.5

 

6.3
10.5

 

 

 

50

 

Yd11

2600235002100222001800222007
4000310027600250026200210026200
5000370032500300030800260030800
63004500349003700330003100330007.5
8000

 

35~38.5

 

3×2.5

 

6.3
6.6
10.5

 

 

YNd11

630038600510036500430036500
10000740045600600043200510043200
125008700540007100511006000511008
160001050066800850063300720063300
2000012400786001010074400850074400
2500014600929001190088000101008800010
31500174001102001420010440012000104400

Note: Due to continuous product improvements, the data provided in this sample is for reference only; please contact our company in time to obtain the latest dimensions.